SINOTIMER ATO-SSR-TH120AA User Manual

SINOTIMER ATO-SSR-TH120AA User Manual



Features

  • Two mounting hole types and sizes
  • Alarm function (overheat prevention)
    : alarm indicator (red), disconnect output, alarm output
  • Improved dielectric strength: 4,000 VACSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1 (some are 2,500 VACSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1 models)
  • Rated input voltage : 4 – 30 VDC SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2, 24 VACSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1, 90 – 240 VACSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
  • Rated load voltage: 24 – 240 VACSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1, 48 – 480 VACSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
  • Rated load current: 15 A, 30 A, 40 A, 50 A, 75 A
  • High heat dissipation efficiency with ceramic PCB and integrated heatsink
  • Zero cross turn-on/Random turn-on models available
  • Input indicator (green)
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 3

Ordering Information

SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 1

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.

❶ Type
No mark: detachable heatsink
H: Integrated heatsink
 Number of the control phase
2: 2-phase
3: 3-phase
❸ Rated input voltage
1: 4 – 30 VDC SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2
2: 24 VAC SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
4: 90 – 240 VAC SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
❹ Rated load voltage
2: 24 – 240 VAC SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
4: 48 – 480 VAC SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
❺ Rated load current (resistive load)
Number: rated load current (unit: A)
❻ Function
No mark: Zero cross turn-on
R: Random turn-on
Product Components

  • Product
  • Instruction manual

Specifications

■ Input

Rated input voltage range4 – 30 VDC24VACrms (50/60 Hz)90 – 240 VACrms  (50/60 Hz)
Allowable input voltage range4 – 32 VDCSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 219 26.4 VACrms SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
(50/60 Hz)
85 – 264 VACrms SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1 (50/60 Hz)
Max. input current25 mA15 mA25 mA
Operating voltage≥ 4 VDCSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2≥ 19 VACrms SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1≥ 85 VACrms SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
Releasing voltage≤ 1 VDCSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2≤ 4 VACrms SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1≤ 10 VACrms SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 1
Operating timeZero cross turn-on< 0.5 cycle of load power + 1 ms≥ 1.5 cycle of load power + 1 ms≤1.5 cycles of load power + 1 ms
Random turn-on≤ 1 ms
Releasing time≤ 0.5 cycle of load power + 1 ms≤ 1.5 cycle of load power + 1 ms≤ 1.5 cycles of load power + 1 ms

■ Output

Rated load voltage range24 – 240 VACrms-,- (50/60 Hz)
Allowable load voltage range24 – 264 VACrms,∼(50/60 Hz)
Rated
load current
Resistive load (AC-51)¹)15 Arms30 Arms50 Arms75 Arms
Min. load current0.15 Arms0.2 Arms0.5 Arms0.5 Arms
Max. 1 cycle surge current (60 Hz)250 A400 A1000 A1000 A
Max. non-repetitive surge current (I2t, t = 8.3 ms)340 A²s1000 A²s4000 A²s4000 A²s
Peak voltage (non-repetitive)600 V
Leakage current (Ta = 25 °C)≤ 10 mArms (240 VAC—/60 Hz)
Output ON voltage drop [Vpk] (max. load current)≤ 1.6 V
Static off state dv/dt500 V/ps
Rated load voltage range48 – 480 VACrms– (50/60 Hz)
Allowable load voltage range48 – 528 VACrms- (50/60 Hz)
Rated
load current
Resistive load (AC-51) `us15 Arms30 Arms40 Arms50 Arms75 Arms
Min. load current0.5 Arms
Max. 1 cycle surge current (60 Hz)300 A500 A500 A1000 A1000 A
Max. non-repetitive surge current (Pt, t = 8.3 ms)350A²s1000 A²s1000A²s4000 A²s4000 A²s
Peak voltage (non-repetitive)1200 V (zero cross turn-on), 1000 A (random turn-on)
Leakage current (Ta = 25 °C)≤ 10 mArms (480 VAC-/60 Hz)
Output ON voltage drop Risk) (max. load current)≤ 1.6 V
Static off state dv/dt500 V/ps

01) AC-51 is utilization category at IEC60947-4-3.

Rated input voltage range4 – 30 VDC (50/60 Hz) 24 VACrms∼(50/60 Hz) 90 – 240 VACrms ∼
Load voltage≤ 30 VDCSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2≤ 30 VDCSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2≤ 30 VDCSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 2
Load current≤ 100 mA≤ 50 mA≤ 50 mA
Turn-off time≤ 20 ms≤ 40 ms≤ 40 ms
  • Overheat prevention function is when SSR internal temperature is overheated, the load output is cut off to prevent internal device damage and also the alarm indicator and alarm output turn ON.

■ Gener specifications

Dielectric strength (Wins) : 24-240 VAC—Rated load current 15 / 30 A
: 2500 VAC∼ 50/60 Hz for 1 min (input-output, input/output-case)
Rated load current 50/ 75 A
: 4000 VAC∼ 50/60 Hz for 1 min (input-output, input/output-case)
Dielectric strength (Vrms) : 48-480 VAC–4000 VAC∼ 50/60 Hz for 1 min (input-output, input/output-case)
Insulation resistance100 MD (500 VDC= megger)
(input-output, input/output-case)
Indicatorinput indicator (green), alarm indicator (red)
Vibration0.75 mm double amplitude at a frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration (malfunction)0.5 mm double amplitude at a frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 10 min
Shock300 m/s² (= 30 6) in each X, Y, Z direction for 3 times
Shock (malfunction)100 m/s² (= 10 G) in each X, Y, Z direction for 3 times
Ambient temperature¹-30 to 80°C (in case of the rated input voltage 90- 240 VAC—: -30 to 70 °C), storage: -30 to 100°C
(no freezing or condensation)
Ambient humidity45 to 8.5%RH, storage: 45 to 85%RH (no freezing or condensation)
Input terminal connection / alarm output terminal connection≥ 1 x 0.5 mm²(1 xAWG 20),
≥ 1x 1.5 mm²(1 x AWG 16) or S 2>: 1.5 mm² (2 x AWG 16)
Output terminal connection² )1 x 1.5 mm²(1 x AWG 16),
≥ 1x 16 mm²(1 xAWG 6) or < 2x 6 mm²(2 x AWG 10)
Input terminal fixed torque0.75 to 0.95 N m
Output terminal fixed torque1.6 to 2.2 N m
ApprovalSINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - icpn 3
  1. Refer to the ‘SSR Derating Curve’ in the product manual because the capacity of the rated load current is differ depending on the ambient temperature.
  2. Connect the wire met the capacity of the load current to the output terminal.
Weight (packaged)
Detachable heatsink type≈, 275 g (≈ 365 g)
Integrated heatsink type15 /30/40A≈, 686g(≈1896g)
50 A≈ 1268 g (≈ 1508 g)
75 A≈ 2064 g (≈ 2354 g)

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.
    A Input indicator (green)
    B Alarm indicator (red)
  • When installing to the panel, tighten the detachable heatsink type screw with a torque of 2.5 to 3 N m, in case of the integrated heatsink type screw, the tightening torque with 1.35 N m.
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 6

■ Detachable heatsink type

■ Integrated heatsink type
• Rated load current 15 / 30 / 40 A
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 7
• Rated load current 50 A
• Rated load current 75 ASINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 2

■ Panel cut-out

• Detachable heatsink type• Integrated heatsink type (rated load current 15 / 30 / 40 A)
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 3
• Integrated heatsink type (rated load current 50 A)• Integrated heatsink type (rated load current 75 A)
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 4

■ Cooling fan mounting hole

• Rated load current 30 / 40 A• Rated load current 50 / 75 A
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 5

SSR Derating Curve

  • The heatsink of the curves is dedicated for the SRH2/SRH3.
  • Install SR2 / SR3 Series on the metal plate (min. 130 × 120 mm).
  • Be aware that the ambient temperature and the derating curve are different by the rated input voltage when using the product.
  • SINOTIMER ATO-SSR-TH120AA User Manual When installing multiple SSRs, be sure to keep space between SSRs for heat radiation. When installing SSRs horizontally (input part and output part on the same height), be sure to supply less than 50 % of the rated load current.
  • SSR derating curves obtained approval from the UL certification authority.
■ SR(H)2 / SR(H)3-1215■ SR(H)2 / SR(H)3-1415 / 1415R / 2415
■ SR(H)2 / SR(H)3-4215■ SR(H)2 / SR(H)3-4415
■ SR(H)2 / SR(H)3-1230■ SR(H)2 / SR(H)3-1430 / 1430R / 2430
■ SR(H)2 / SR(H)3-4230■ SR(H)2 / SR(H)3-4430
■ SR(H)2 / SR(H)3-1440 / 1440R / 2440■ SR(H)2 / SR(H)3-4440
■ SR(H)2 / SR(H)3-1250 / 1450 / 1450R / 2450■ SR(H)2 / SR(H)3-4250 / 4450
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 14
■ SR(H)2 / SR(H)3-4275 / 4475■ SR(H)2 / SR(H)3-1275 / 1475 / 1475R / 2475
SINOTIMER ATO SSR TH120AA 2 or 3 Phase SSR Solid State Relay - Fig 15